11
Features and Main Functions
Section 1-1
Analog Settings (All Models)
Changing Settings Using
Analog Adjustment
By adjusting the analog adjuster with a Phillips screwdriver, the value in the
Auxiliary Area can be changed to any value between 0 and 255. This makes it
easy to change set values such as timers and counters without Programming
Devices.
Changing Settings Using
External Analog Setting
Inputs
External analog values of 0 to 10 V (resolution: 256) are converted to digital
values and stored in a word in the AR Area. This enables applications that
require on-site adjustment of settings that do not demand a particularly high
degree of accuracy, such as for example, a setting based on changes in out-
door temperatures or potentiometer inputs.
CNTX
A642
Phillips screwdriver
Analog adjuster
Ladder program
Example: The production quantity could be changed by
changing the counter set value from 100 to 150.
Turning the control on the CP1H changes the
PV in A642 between 0000 and 0255 (00 and
FF hex).
(During the adjustment, the value in A642 is
displayed from 00 to FF on the 7-segment
display.)
TIMX
A643
0 to 10 V
External analog setting
input connector
Potentiometer,
temperature sensor, etc.
Ladder program
Example: The production quantity could be changed by
changing the timer set value from 100 to 150.
When a voltage (0 to 10 V) is input
from a device such as a potentiometer
to the external analog setting input, the
PV in A643 is refreshed between 0000
and 0100 hex (0 to 256).
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...