669
Auxiliary Area Allocations by Address
Appendix D
A508
A508.09 Differentiate
Monitor
Completed
Flag
ON when the differentiate monitor
condition has been established dur-
ing execution of differentiation moni-
toring.
(This flag will be cleared to 0 when
differentiation monitoring starts.)
ON: Monitor
condition
established
OFF: Not yet
established
Retained
Cleared
---
---
A508.11 Trace Trig-
ger Monitor
Flag
ON when a trigger condition is estab-
lished by the Trace Start Bit
(A508.14). OFF when the next Data
Trace is started by the Sampling
Start bit (A508.15).
ON: Trigger
condition
established
OFF: Not yet
established or
not tracing
Retained
Cleared
---
---
A508.12 Trace Com-
pleted Flag
ON when sampling of a region of
trace memory has been completed
during execution of a Trace.
OFF when the next time the Sam-
pling Start Bit (A508.15) is turned
ON.
ON: Trace
completed
OFF: Not trac-
ing or trace in
progress
Retained
Cleared
---
---
A508.13 Trace Busy
Flag
ON when the Sampling Start Bit
(A508.15) is turned ON. OFF when
the trace is completed.
ON: Trace in
progress
OFF: Not trac-
ing (not sam-
pling)
---
---
---
---
A508.14 Trace Start
Bit
Turn this bit ON to establish the trig-
ger condition. The offset indicated by
the delay value (positive or negative)
determines which data samples are
valid.
ON: Trace trig-
ger condition
established
OFF: Not
established
---
---
---
---
A508.15 Sampling
Start Bit
When a data trace is started by turn-
ing this bit ON from the CX-Program-
mer, the PLC will begin storing data
in Trace Memory by one of the three
following methods:
1) Data is sampled at regular inter-
vals (10 to 2,550 ms).
2) Data is sampled when TRSM(045)
is executed in the program.
3) Data is sampled at the end of
every cycle.
The operation of A508.15 can be
controlled only from the CX-Pro-
grammer.
OFF to ON:
Starts data
trace (sam-
pling)
Turned ON
from Program-
ming Device.
---
---
---
---
A510 to
A511
All
startup Time These words contain the time at
which the power was turned ON. The
contents are updated every time that
the power is turned ON. The data is
stored in BCD.
A510.00 to A510.07: Second (00 to
59)
A510.08 to A510.15: Minute (00 to
59)
A511.00 to A511.07: Hour (00 to 23)
A511.08 to A511.15: Day of month
(01 to 31)
See Function
column.
Retained
See
Function
column.
Refresh-
ed when
power is
turned
ON.
---
A512 to
A513
All
Power Inter-
ruption Time
These words contain the time at
which the power was interrupted.
The contents are updated every time
that the power is interrupted. The
data is stored in BCD.
A512.00 to A512.07: Second (00 to
59)
A512.08 to A512.15: Minute (00 to
59)
A513.00 to A513.07: Hour (00 to 23)
A513.08 to A513.15: Day of month
(01 to 31)
(These words are not cleared at star-
tup.)
See Function
column.
Retained
Retained
Written at
power
interrup-
tion
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...