144
Overview of I/O Memory Area
Section 4-1
4-1-2
Overview of the Data Areas
■
CIO Area
It is not necessary to input the “CIO” acronym when specifying an address in
the CIO Area. The CIO Area is generally used for data exchanges, such as
I/O refreshing with PLC Units. Words that are not allocated to Units may be
used as work words and work bits in the program.
Note
The parts of the CIO Area that are labelled “not used” may be used in pro-
gramming as work bits. In the future, however, unused CIO Area bits may be
used when expanding functions. Always use Work Area bits first.
I/O Area (Inputs: CIO 0 to CIO 16, Outputs: CIO 100 to CIO 116)
These words are allocated to built-in I/O terminals of CP1H CPU Units and
CP-series Expansion Units or Expansion I/O Units. Input words and output
bits that aren’t allocated may be used in programming.
Built-in Analog Input Area (Built-in Analog Inputs: CIO 200 to CIO 203,
CIO 210 to CIO 211) (XA CPU Units Only)
These words are allocated to built-in analog I/O terminals of CP1H XA CPU
Units. Words that aren’t used in data links may be used in programming.
Data Link Area
These words are used when the Controller Link auto-setting area is set to the
link area or for PLC links. Words that aren’t used in data links may be used in
programming.
X and Y CPU Units
XA CPU Units
15
00
CIO 0
CIO 16
CIO 17
CIO 999
CIO 1000
CIO 1200
CIO 1199
CIO 1500
CIO 1499
CIO 1900
CIO 1899
CIO 1999
CIO 2000
CIO 2959
CIO 2960
CIO 6143
(CIO 3199)
CIO 3200
CIO 3799
CIO 3800
CIO 3100
CIO 100
CIO 116
CIO 99
CIO 117
Word
Bit
Input Area
Not used (see note).
Output Area
Not used (see note).
Data Link Area
Work Area
CPU Bus Unit Area
(25 words/Unit)
Not used (see note).
Special Unit Area
(10 words/Unit)
Not used (see note).
Serial PLC Link Area
DeviceNet Area
Work Area
15
0
CIO
0
CIO 16
CIO 17
CIO
999
CIO 1000
CIO 1200
CIO 1199
CIO 1500
CIO 1499
CIO 1900
CIO 1899
CIO 1999
CIO 2000
CIO 2959
CIO 2960
CIO
6143
(CIO 3199)
CIO 3200
CIO 3799
CIO 3800
CIO 3100
CIO 100
CIO 116
CIO
99
CIO 117
Built-in Analog I/O Areas
CIO 200
CIO 211
CIO
199
CIO 212
Word
Bit
Input Area
Not used (see note).
Output Area
Not used (see note).
Data Link Area
Work Area
CPU Bus Unit Area
(25 words/Unit)
Not used (see note).
Special Unit Area
(10 words/Unit)
Not used (see note).
Serial PLC Link Area
DeviceNet Area
Work Area
Not used (see note).
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...