218
High-speed Counters
Section 5-2
Y CPU Units
Input Terminal Arrangement
Input Function Settings in the PLC Setup
The CPU Unit’s built-in inputs can be set for high-speed counter inputs in the
PLC Setup’s Built-in Input Tab. (When an input is set for use as a high-speed
counter input, the corresponding words and bits cannot be used for general-
purpose (normal) inputs, input interrupts, or quick-response inputs.)
+
−
COM
01
05
11
01
03
05
NC
00
04
10
00
02
04
A0+
B0+
Z0+
A0+
B0+
Z0+
A0
−
B0
−
Z0
−
A0
−
B0
−
Z0
−
High-speed counter 0
(Phase B, Decrement, or
Direction input)
High-speed counter 0
(Phase Z or Reset input)
High-speed counter 0
(Phase A, Increment, or
Count input)
High-speed counter 1
(Phase B, Decrement, or
Direction input)
High-speed counter 1
(Phase Z or Reset input)
High-speed counter 1
(Phase A, Increment, or
Count input)
High-speed counter 2
(Phase B, Decrement, or
Direction input)
High-speed counter 3
(Phase B, Decrement, or
Direction input)
High-speed counter 2
(Phase Z or Reset input)
Upper Terminal Block
Inputs
(CIO 0)
Inputs (CIO 1)
High-speed counter terminals
High-speed counter 2
(Phase A, Increment, or
Count input)
High-speed counter 3
(Phase Z or Reset input)
High-speed counter 3
(Phase A, Increment, or
Count input)
Input terminal
block
Bit function when the high-speed counter is enabled by
selecting “Use high-speed counter
@
” in the PLC Setup
Word
Bit
---
A0
High-speed counter 0 (Phase A, Increment, or Count input)
---
B0
High-speed counter 0 (Phase B, Decrement, or Direction input)
---
Z0
High-speed counter 0 (Phase Z or reset input)
---
A1
High-speed counter 1 (Phase A, Increment, or Count input)
---
B1
High-speed counter 1 (Phase B, Decrement, or Direction input)
---
Z1
High-speed counter 1 (Phase Z or reset input)
CIO 0
00
---
01
High-speed counter 2 (Phase A, Increment, or Count input)
04
High-speed counter 2 (Phase B, Decrement, or Direction input)
05
High-speed counter 2 (Phase Z or reset input)
10
High-speed counter 3 (Phase A, Increment, or Count input)
11
High-speed counter 3 (Phase B, Decrement, or Direction input)
CIO 1
00
High-speed counter 3 (Phase Z or reset input)
01 to 05
---
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...