Wiring Methods
Section 3-5
circuiting the plus and minus terminals. If the range is set for 1 to 5 V and
4 to 20 mA, however, the Open-circuit Detection Flag will turn ON when
the plus and minus terminals are short-circuited.
Terminal Block Wiring
When wiring the analog I/O terminal block, either use ferrules or solid wires.
• Wire the terminal block while it is mounted to the CPU Unit and do not
remove it from the CPU Unit after completing wiring.
• To make the connection, insert the ferrule or solid wire into the round hole
in the terminal block it locks inside.
• To disconnect the wiring, press the release button in with a small flat-
blade screwdriver and pull the line out while the lock is released.
The screwdriver shown below is recommended for disconnecting wiring.
Recommended Screwdriver
Recommended Ferrules and Crimp Tools
The following crimp terminals and crimping tool are recommended.
The following ferrules can also be used.
Model
Manufacturer
SZF1
Phoenix Contact
Crimp terminals
Crimping tool
PHOENIX CONTACT
Phoenix Contact
AI-TWIN2
×
0.5-8WH (Product code: 3200933)
UD6 (Product code: 1204436)
Manufacturer
Model
Applicable wire
Phoenix Contact
AI-0.5-10
0.5 mm
2
(AWG20)
AI-0.75-10
0.75 mm
2
(AWG18)
AI-1.5-10
1.25 mm
2
(AWG16)
Nihon Weidmuller Co., Ltd.
H 0.5/16 D
0.5 mm
2
(AWG20)
H 0.75/16 D
0.75 mm
2
(AWG18)
H 1.5/16 D
1.25 mm
2
(AWG16)
2-conductor shielded
twisted-pair cable
Ferrules
Release button
3.5 mm
0.6 mm
Side
Front
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...