404
Analog Output Units
Section 7-3
Allocation of Output
Words
Four output words are allocated, beginning from the first word following the
last I/O word allocated to the CPU Unit or already-connected Expansion I/O
Unit or Expansion Unit.
Writing the Range Code
Write the output use and the range code to words n+1 and n+2. The D/A con-
version will start when the set data is transferred from the CPU Unit to the
Analog Output Unit.
■
Range Code
• The Analog Output Unit will not start converting analog I/O values until the
range code has been written. The output will be 0 V or 0 mA.
• From when the range code has been written until data in the analog out-
put convertible range is written, 0 V or 0 mA will be output in the 0 to 10 V,
-10 to +10 V, and 0 to 20 mA ranges, and 1 V or 4 mA will be output in the
1 to 5 V and 4 to 20 mA ranges.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
3. Ladder Program
Words n+1 to n+4
Analog Output Unit
15 0
1 0 0
0
0
0
0
8
7
6
5
4
3
2
1
Wd n+1
15 0
1 0 0
0
0
0
0
8
7
6
5
4
3
2
1
0
0
Analog output 2
Analog output 1
Analog output 4
Analog output 3
Set to 1.
Set to 1.
Wd n+2
0
1
Range code
Analog output signal range
−
10 to 10 V
0 to 10 V
1 to 5 V
0 to 20 mA
4 to 25 mA
000
001
010
011
100
Output use
No
Yes
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...