62
Specifications
Section 2-2
Analog I/O Specifications
Note
(1) The built-in analog input switch is used for toggling between voltage input
and current input. (The default setting at the time of shipping is for voltage
input.)
(2) Switching between 1/6,000 and 1/12,000 resolution is done in the PLC
Setup. The same resolution setting is used for all I/O words. It is not pos-
sible to set them individually.
(3) The total conversion time is the total of the conversion times for all the
points that are used. It would be 6 ms for 4 analog inputs and 2 analog
outputs.
(4) When the analog current output is within 0 to 20 mA, the accuracy cannot
be ensured if below 0.2 mA.
Model
CP1H-XA40DR-A
CP1H-XA40DT-D
CP1H-XA40DT1-D
Item
Voltage I/O (See note 1.)
Current I/O (See note 1.)
Analog
Input Sec-
tion
Number of
inputs
4 inputs (4 words allocated)
Input signal
range
0 to 5 V, 1 to 5 V, 0 to 10 V, or
−
10 to 10 V
0 to 20 mA or 4 to 20 mA
Max. rated input
±
15 V
±
30 mA
External input
impedance
1 M
Ω
min.
Approx. 250
Ω
Resolution
1/6000 or 1/12000 (full scale) (See note 2.)
Overall accu-
racy
25
°
C:
±
0.3% full scale/0 to 55
°
C:
±
0.6% full
scale
25
°
C:
±
0.4% full scale/0 to 55
°
C:
±
0.8% full
scale
A/D conversion
data
Full scale for
−
10 to 10 V: F448 (E890) to 0BB8 (1770) hex
Full scale for other ranges: 0000 to 1770 (2EE0) hex
Averaging func-
tion
Supported (Set for individual inputs in the PLC Setup.)
Open-circuit
detection func-
tion
Supported (Value when disconnected: 8000 hex)
Analog Out-
put Section
Number of out-
puts
2 outputs (2 words allocated)
Output signal
range
0 to 5 V, 1 to 5 V, 0 to 10 V, or
−
10 to 10 V
0 to 20 mA or 4 to 20 mA (See note 4.)
Allowable exter-
nal output load
resistance
1 k
Ω
min.
600
Ω
max.
External output
impedance
0.5
Ω
max.
---
Resolution
1/6000 or 1/12000 (full scale) (See note 2.)
Overall accu-
racy
25
°
C:
±
0.4% full scale/0 to 55
°
C:
±
0.8% full scale
D/A conversion
data
Full scale for
−
10 to 10 V: F448 (E890) to 0BB8 (1770) hex
Full scale for other ranges: 0000 to 1770 (2EE0) hex
Conversion time
1 ms/point (See note 3.)
Isolation method
Photocoupler isolation between analog I/O terminals and internal circuits. No isolation
between analog I/O signals.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...