632
Auxiliary Area Allocations by Function
Appendix C
Memory Cassette Information
Information on Read Protection Using a Password
Name
Address
Description
Access
Updated
Memory Cassette Access
Status
A342
A342.03: ON when data is being written to the Memory
Cassette or the Memory Cassette is being ini-
tialized. OFF when processing has been com-
pleted.
A342.04: ON when data is being read from the Memory
Cassette. OFF when processing has been
completed.
A342.05: ON when data is being compared with data on
the Memory Cassette. OFF when processing
has been completed.
A342.07: ON when an error occurs in initializing the
Memory Cassette.
OFF the next time the Memory Cassette is
accessed normally (initialized, written, read, or
compared).
A342.08: ON when an error occurs in writing the Mem-
ory Cassette.
OFF the next time the Memory Cassette is
accessed normally (initialized, written, read, or
compared).
A342.10: ON when an error occurs in reading or com-
paring the Memory Cassette.
OFF the next time the Memory Cassette is
accessed normally (initialized, written, read, or
compared).
A342.12: ON when the data in the CPU Unit is not the
same as the data in the Memory Cassette
when a verification operation is performed.
OFF the next time the Memory Cassette is
accessed normally (initialized, written, read, or
compared).
A342.13: ON when the Memory Cassette is being
accessed. OFF when processing has been
completed.
A342.15: ON when a Memory Cassette is mounted.
OFF when a Memory Cassette is not mounted.
Read-only
Memory Casette Verifica-
tion Results
A494
Stores the results of comparing data in the Memory Cas-
sette and CPU Unit. Each bit turns ON to indicate status.
A494.00: User program is different.
A494.01: Function block sources are different.
A494.02: Parameter area is different.
A494.03: Symbol table is different.
A494.04: Comments are different.
A494.05: Program indices are different.
A494.06: Data memory is different.
A494.07: DM initial values are different.
Read-only
Name
Address
Description
Access
Updated
UM Read Protection Flag
A99.00
Indicates whether the entire user program in the PLC is
read-protected.
OFF: UM not read-protected.
ON: UM read-protected.
Read-only
Task Read Protection Flag
A99.01
Indicates whether read protection is set for individual
tasks.
OFF: Tasks not read-protected.
ON: Tasks read-protected.
Read-only
Program Write Protection for
Read Protection
A99.02
Indicates whether the program is write-protected.
OFF: Write-enabled.
ON: Write-protected.
Read-only
Enable/Disable Bit for Pro-
gram Backup
A99.03
Indicates whether creating a backup program file (.OBJ)
is enabled or disabled.
OFF: Enabled.
ON: Disabled.
Read-only
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...