408
Analog I/O Units
Section 7-4
Main Analog I/O Unit
Specifications
Analog I/O Units are connected to the CP1H CPU Unit. Up to seven Units can
be connected, including any other Expansion Units and Expansion I/O Units
that are also connected.
Note
(1) The conversion time is the total time for 2 analog inputs and 1 analog out-
put.
(2) With analog outputs it is possible to use both voltage outputs and current
outputs at the same time. In this case however, the total output current
must not exceed 21 mA.
CP1H CPU Unit
A maximum of 7 Expansion Units or Expansion I/O Units can be connected.
IN
OUT
V O UT
CO M
I IN 1
V IN 2
CO M2
I O U T
V IN 1
CO M1
I IN 2
MAD01
C H
C H
E X P
IN
00
C H
C H
02
04
06
08
10
OUT
01
C OM
03
05
07
09
11
C OM
CO M
C OM
03
CO M
06
00
01
02
04
05
07
00 01 02 03 04 05 06 07
08 09 10 11
20EDR1
C H
00 01 02 03 04 05 06 07
N C
N C
N C
C H
E X P
IN
00
02
01
C OM
03
C OM
05
07
04
06
C H 00 01 02 03
08 09 10 11
8ED
E X P
CPM1A-20EDR1
Expansion I/O Unit
CPM1A-8ED
Expansion I/O Unit
CPM1A-MAD01
Analog I/O Unit
1 analog output
2 analog inputs
Item
Voltage I/O
Current I/O
Analog
Input
Section
Number of inputs
2
Input signal range
0 to 10 V/1 to 5 V
4 to 20 mA
Max. rated input
±
15 V
±
30 mA
External input impedance
1 M
Ω
min.
250
Ω
rated current
Resolution
1/256
Accuracy
1.0% full scale
A/D conversion data
8-bit binary
Analog
Output
Section
(See
note 2.)
Number of outputs
1
Output signal range
0 to 10 V or
−
10 to 10 V
4 to 20 mA
Max. external output current
5 mA
---
Allowable external output load resistance
---
350
Ω
Resolution
1/256 (1/512 when the output signal range is
−
10 to 10 V)
Accuracy
1.0% of full scale
Set data
8-bit signed binary
Conversion time
10 ms max. per Unit (See note 1.)
Isolation method
Photocoupler isolation between I/O terminals and PC signals.
No isolation between analog I/O signals.
Current consumption
5 VDC: 66 mA max., 24 VDC: 66 mA max.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...