274
Pulse Outputs
Section 5-3
Origin Return
Acceleration Rate
Sets the motor's acceleration rate when the origin return operation starts.
Specify the amount to increase the speed (Hz) per 4-ms interval.
Origin Return
Deceleration Rate
Sets the motor's acceleration rate when the origin return function is decelerat-
ing. Specify the amount to decrease the speed (Hz) per 4-ms interval.
Executing an Origin Return
Note
An instruction execution error will occur if the origin is not determined (relative
coordinate system) when ORG(889) is executed to perform an origin return
operation.
5-3-7
Pulse Output Procedures
Single-phase Pulse Output without Acceleration/Deceleration
The number of output pulses setting cannot be changed during positioning.
■
PULS(886) and SPED(885)
P
C
ORG(889)
P: Port specifier (Pulse output 0: #0000, Pulse output 1: #0001)
Pulse output 0: #0000
Pulse output 1: #0001
Pulse output 2: #0002
Pulse output 3: #0003
C: Control data
(Origin return and CW/CCW method: #1000, Origin search and pulse
+ direction method: #1100)
Determine the pulse output method,
output frequency, and port.
•
Pulse output method
•
CW/CCW inputs: Pulse outputs 0 to 3
•
Pulse + direction inputs: Pulse outputs 0 to 3
Pulse outputs 0 and 1 use the same pulse output method.
•
Output frequency
•
X/XA models:
Unit version 1.1 or later
1 Hz to 100 kHz (1 Hz units), 4 outputs
Unit version 1.0 or earlier
Pulse outputs 0 and 1: 1 Hz to 100 kHz (1 Hz units)
Pulse outputs 2 and 3: 1 Hz to 30 kHz (1 Hz units)
•
Y models:
Pulse outputs 0 and 1: 1 Hz to 1 MHz (1 Hz units)
Pulse outputs 2 and 3: 1 Hz to 100 kHz (1 Hz units)
Wire the outputs.
PLC Setup settings
•
Enable/disable the origin search function. Set the
various origin search parameters if the origin search
function is enabled.
Ladder program
•
PULS(886): Specify port number and set the number of
output pulses.
•
SPED(885): Specify port number and set the output
method (CW/CCW method or Pulse + direction method)
and pulse output control without acceleration/deceleration.
•
INI(880): Specify port number and stop pulse output when
necessary.
•
PRV(881): Specify port number and read pulse output PV
when necessary.
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...