420
Analog I/O Units
Section 7-4
1 to 5 V
The 1- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C (
−
300 to 6300). Inputs
between 0.8 and 1 V are expressed as two’s complements. If the input falls
below 0.8 V, open-circuit detection will activate and converted data will be
8000.
0 to 20 mA
The 0- to 20-mA range corresponds to the hexadecimal values 0000 to 1770
(0 to 6000). The entire data range is FED4 to 189C (
−
300 to 6300). A negative
voltage is expressed as a two’s complement.
4 to 20 mA
The 4- to 20-mA range corresponds to the hexadecimal values 0000 to 1770
(0 to 6000). The entire data range is FED4 to 189C (
−
300 to 6300). Inputs
between 3.2 and 4 mA are expressed as two’s complements. If the input falls
below 3.2 mA, open-circuit detection will activate and converted data will be
8000.
1 V
5 V 5.2 V
0.8 V
FED4 (
−
300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 mA
20 mA 21 mA
−
1 mA
FED4 (
−
300)
189C (6300)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
4 mA
20 mA 20.8 mA
3.2 mA
FED4 (
−
300)
189C (6300)
1770 (6000)
0000 (0)
0 mA
Converted Data
Hexadecimal (Decimal)
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...