210
High-speed Counters
Section 5-2
Auxiliary Area Data
Allocation
Count values
Linear mode: 80000000 to 7FFFFFFF hex
Ring mode: 00000000 to Ring SV
(The Ring SV (Circular Max. Count) is set in the PLC Setup and the setting
range is 00000001 to FFFFFFFF hex.)
High-speed counter PV storage locations
High-speed counter 0: A271 (leftmost 4 digits) and A270 (rightmost 4 digits)
High-speed counter 1: A273 (leftmost 4 digits) and A272 (rightmost 4 digits)
High-speed counter 2: A317 (leftmost 4 digits) and A316 (rightmost 4 digits)
High-speed counter 3: A319 (leftmost 4 digits) and A318 (rightmost 4 digits)
Target value comparison interrupts or range comparison interrupts can be
executed based on these PVs.
Note
The PVs are refreshed in the overseeing processes at the start of each
cycle. Use PRV(881) to read the most recent PVs.
Data format: 8 digit hexadecimal
Range in linear mode: 80000000 to 7FFFFFFF hex
Range in ring mode: 00000000 to Ring SV (Circular Max. Count)
Control
method
Target value comparison
Up to 48 target values and corresponding interrupt task numbers can be reg-
istered.
Range comparison
Up to 8 ranges can be registered, with a separate upper limit, lower limit, and
interrupt task number for each range.
Counter reset method
Select one of the following methods in the PLC Setup.
•Phase-Z + Software reset
The counter is reset when the phase-Z input goes ON while the Reset Bit is
ON.
•Software reset
The counter is reset when the Reset Bit goes ON.
(Set the counter reset method in the PLC Setup.)
Note
Operation can be set to stop or continue the comparison operation
when the high-speed counter is reset.
Item
Specification
Function
High-speed counter number
0
1
2
3
PV storage words
Leftmost 4 digits
A271
A273
A317
A319
Rightmost 4 digits
A270
A272
A316
A318
Range Comparison Con-
dition Met Flags
Range 1 Comparison Condition Met Flag
A274.00
A275.00
A320.00
A321.00
Range 2 Comparison Condition Met Flag
A274.01
A275.01
A320.01
A321.01
Range 3 Comparison Condition Met Flag
A274.02
A275.02
A320.02
A321.02
Range 4 Comparison Condition Met Flag
A274.03
A275.03
A320.03
A321.03
Range 5 Comparison Condition Met Flag
A274.04
A275.04
A320.04
A321.04
Range 6 Comparison Condition Met Flag
A274.05
A275.05
A320.05
A321.05
Range 7 Comparison Condition Met Flag
A274.06
A275.06
A320.06
A321.06
Range 8 Comparison Condition Met Flag
A274.07
A275.07
A320.07
A321.07
Comparison In-progress
Flags
ON when a comparison operation is being exe-
cuted for the high-speed counter.
A274.08
A275.08
A320.08
A321.08
Overflow/Underflow Flags
ON when an overflow or underflow has
occurred in the high-speed counter’s PV.
(Used only when the counting mode is set to
Linear Mode.)
A274.09
A275.09
A320.09
A321.09
Count Direction Flags
0: Decrementing
1: Incrementing
A274.10
A275.10
A320.10
A321.10
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...