158
Data Link Area
Section 4-4
4-4
Data Link Area
Data Link Area addresses range from CIO 1000 to CIO 1199
(bits CIO 1000.00 to CIO 1199.15). Words in the Link Area are used for data
links when
LR
is set as the data link area for Controller Link Networks. It is
also used for PLC Links. Words in the Link Area can be used in the program
when
LR
is not set as the data link area for Controller Link Networks and PLC
Links are not used.
Data links can be generated automatically (using the same number of words
for each node) or manually. When a user defines the data links manually, any
number of words can be assigned to each node, and nodes can be made
receive-only or transmit-only. Refer to the
Controller Link Units Operation
Manual (W309
)
for details.
Forcing Bit Status
Bits in the Data Link Area can be force-set and force-reset.
Links to C200HX/HG/HE,
C200HS, and C200H PLCs
Link Area words CIO 1000 to CIO 1063 in CP1H CPU Units correspond to
Link Relay Area words LR 0 to LR 63 for data links created in
C200HX/HG/HE(-Z) PLCs. When converting C200HX/HG/HE(-Z), C200HS,
or C200H programs for use in CP1H CPU Units, change addresses LR 0
through LR 63 to Link Area addresses CIO 1000 through CIO 1063.
Link Area Initialization
The contents of the Link Area will be cleared in the following cases:
1.
When the operating mode is changed from PROGRAM mode to
RUN/MONITOR mode or vice-versa and the IOM Hold Bit is OFF
2.
When the power is cycled
3.
When the Data Link Area is cleared from the CX-Programmer
4.
When PLC operation is stopped when a fatal error other than an
FALS(007) error occurs. (The contents of the Link Area will be retained if
FALS(007) is executed.)
Controller
Link Unit
CPU Unit
Linked words
Controller
Link Unit
CPU Unit
Controller
Link Unit
CPU Unit
Controller Link Network
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...