393
Analog Input Units
Section 7-2
■
0 to 20 mA Inputs
■
4 to 20 mA Inputs
Averaging Function
For analog inputs, the averaging function operates when the averaging bit is
set to 1. The averaging function outputs the average (a moving average) of
the last eight input values as the converted value. If there is only a slight vari-
ation in inputs, it is handled by the averaging function as a smooth input.
The averaging function stores the average (a moving average) of the last eight
input values as the converted value. Use this function to smooth inputs that
vary at a short interval.
Open-circuit Detection
Function
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
Current in the 0 to 20 mA
range corresponds to hexa-
decimal values 0000 to 1770
(0 to 6,000). The range of
data that can be converted is
FED4 to 189C hex (-300 to
6,300). A negative current is
expressed as two’s comple-
ment.
Current in the 4 to 20 mA
range corresponds to hexa-
decimal values 0000 to 1770
(0 to 6,000). The range of
data that can be converted is
FED4 to 189C hex (-300 to
6,300). Current in the range of
3.2 to 4 mA is expressed as
two’s complement.
If an input is below the range
(i.e., less than 3.2 mA), the
open-circuit detection func-
tion is activated and the data
becomes 8,000.
0 mA
20 mA 21 mA
−
1 mA
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (
−
300)
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (
−
300)
4 mA
20 mA 20.8 mA
3.2 mA
0 mA
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...