583
Troubleshooting
Section 11-2
■
Reference Information
Too Many I/O Points
The number of CP-series Expansion Units, CP-series Expansion I/O Units, or
CJ-series Units connected exceeds the restriction for the number of Units or
words for the system configuration. Turn OFF the power supply and reconfig-
ure the system within the restrictions.
■
Reference Information
I/O Setting Error
An I/O setting error indicates that a Unit is connected that cannot be used in
the system configuration. Turn OFF the power supply and remove the Unit.
■
Reference Information
Error flag
Duplication Error Flag, A401.13
Error code (A400)
80E9
Error information
CPU Bus Unit Duplication Number Flags, A410
Special I/O Unit Duplicate Number Flags, A411 to A416
8.0.
→
e.1.
→
→
→
Too many I/O points, details
Seven-segment display
Probable cause and possible remedy
8.0.
→
e.1.
→ →
4.0.
→
0.0.
→
The total number of words for CP-series Expansion Units and
Expansion I/O Units exceeds the restriction. Configure the system
so that there are no more than 15 input words and 15 output
words allocated to Expansion Units and Expansion I/O Units.
Refer to
1-2-4 Restrictions
on System Configuration.
→
6.0.
→
0.0.
→
The number of CP-series Expansion Units and Expansion I/O
Units exceeds the restriction. Connect a maximum of seven Units.
→
e.0.
→
0.0.
→
The number of CJ-series Units exceeds the restriction. Mount a maximum of two Units.
Error flag
Too Many I/O Points Flag, A401.11
Error code (A400)
80E1
Error information
Too Many I/O Points Details, A407
Seven-segment
display
Probable cause and possible remedy
8.0.
→
e.0.
→
A CJ-series Basic I/O Unit or an I/O Control Unit has been
mounted. These Unit cannot be used. Remove any of these Units.
Error flag
I/O Setting Error Flag, A401.10
Error code (A400)
80E0
Error information
---
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...