149
Overview of I/O Memory Area
Section 4-1
Note
*The following areas of I/O memory will be cleared during mode changes
(between PROGRAM and RUN/MONITOR) unless the IOM Hold Bit is ON:
the CIO Area (I/O Area, Data Link Area, CPU Bus Unit Area, Special I/O Unit
Area, DeviceNet (CompoBus/D) Area, and Internal I/O Areas), Work Area,
Timer Completion Flags, and Timer PVs.
Auxiliary Area Flags and Words
When the IOM Hold Bit is ON, all outputs from Output Units will be maintained
when program execution stops. When the program starts again, outputs will
have the same status that they had before the program was stopped and
instructions will be executed. (When the IOM Hold Bit is OFF, instructions will
be executed after the outputs have been cleared.)
PLC Power ON
In order for all data* in I/O memory to be retained when the PLC is turned ON,
the IOM Hold Bit must be ON and it must be protected in the PLC Setup using
the
IOM Hold Bit Status at Startup
parameter.
Auxiliary Area Flags and Words
PLC Setup
Name
Address
Description
IOM Hold Bit
A500.12
Specifies whether the I/O memory will be retained or not
when the CPU Unit operating mode is changed
(between PROGRAM and RUN/MONITOR) or when the
power is cycled.
OFF: I/O memory is cleared to 0 when the operating
mode is changed.
ON:
I/O memory is retained when the operating mode
is changed between PROGRAM and RUN or
MONITOR.
Name
Address
Description
IOM Hold Bit
A500.12
Specifies whether the I/O memory will be retained or
not when the CPU Unit operating mode is changed
(between PROGRAM and RUN/MONITOR) or when
the power is cycled.
OFF: I/O memory is cleared to 0 when the operating
mode is changed.
ON:
I/O memory is retained when the operating
mode is changed between PROGRAM and
RUN or MONITOR.
Name
Description
Setting
Default
IOM Hold
Bit Status
at Startup
To retain all data in I/O
memory when the PLC
is turned ON, set the
IOM Hold Bit at startup
parameter to hold the
status of the I/O Hold Bit.
OFF:
The IOM Hold Bit is cleared
to 0 when power is cycled.
ON:
The status of the IOM Hold
Bit is retained when power is
cycled.
OFF
(Cleared)
Retained
Power ON
I/O memory
CIO and
other areas
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...