150
I/O Area and I/O Allocations
Section 4-2
4-2
I/O Area and I/O Allocations
Input Bits:
CIO 0.00 to CIO 16.15 (17 words)
Output Bits:
CIO 100.00 to CIO 116.15 (17 words)
The starting words for inputs and outputs are predetermined for CP1H CPU
Unit. Input bits in CIO 0 and CIO 1 and output bits in CIO 100 and CIO 101
are automatically allocated to the built-in I/O on the CPU Unit. CP-series
Expansion Units and CP-series Expansion I/O Units are automatically allo-
cated input bits in words starting from CIO 2 and output bits in words starting
from CIO 102.
Note
CJ-series Basic Units cannot be connected to a CP1H PLCs.
Bits in the I/O Area can be force-set/reset from the CX-Programmer.
The I/O Area will be cleared at the following times:
(1) When the operating mode is changed between PROGRAM mode and
RUN or MONITOR mode
(2) When the power is cycled
(3) When I/O memory is cleared from the CX-Programmer
(4) When operation fails due to a fatal error other than one created by exe-
cuting a FALS(007) instruction (Memory will be retained if operation fails
due to execution of a FALS(007) instruction.)
4-2-1
Overview
CIO 0 and CIO 1 are allocated to the built-in inputs and CIO 100 and CIO 101
are allocated to the built-in outputs on the CPU Unit.
For CP-series Expansion Units and Expansion I/O Units, inputs are allocated
in the order that the Units are connected starting from CIO 2 in the Input Area
and from CIO 102 in the Output Area. (See note.)
A total of up to seven CP-series Expansion Units and Expansion I/O Units can
be connected. The total number of input words and output words must be 17
or less. A fatal error (Too Many I/O Points) will occur if this limit is exceeded,
and operation will stop.
CP1H CPU Unit
Built-in inputs: CIO 0 and
CIO 1 are allocated.
Built-in outputs: CIO 100 and
CIO 101 are allocated.
Expandable up to a total of seven CP-series
Expansion I/O Units and Expansion Units.
Expansion I/O Unit and Expansion Unit inputs:
Words are allocated starting from CIO 2.
Expansion I/O Unit and Expansion Unit outputs:
Words are allocated starting from CIO 102.
Order of connection
Summary of Contents for CP1H CPU UNITS - PROGRAMMING 05-2007
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Page 370: ...336 Analog I O XA CPU Units Section 5 5...
Page 552: ...518 Trouble Shooting Section 8 7...
Page 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 598: ...564 Sample Application Section 9 12...
Page 642: ...608 Standard Models Appendix A...
Page 652: ...618 Dimensions Diagrams Appendix B...
Page 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Page 776: ...742 PLC Setup Appendix G...
Page 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Page 786: ...752 Revision History...