Set Value Generators
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
354
3.6
n
change of set value from effective set value at ramp function generator output
to 0%. This causes a constant braking time from all speeds at ramp func-
tion generator output.
m
The set SS1 stop time
applies to
n
change of set value from effective speed to 0%. This causes a constant braking time
from all speeds.
n
change of set value from 100% to 0% (braking deceleration independent of the in-
stantaneous speed).
More functions:
m
Input value limited by
and
m
Monitoring of the hardware limit switch. The behavior at an active hardware limit switch
can be chosen via
bit 8 and 9. The limit switch monitoring is switched on via
bit 1 = 1.
m
Additional additive input
with format of the 32 bit input
.
m
Transparency mode: Switch off ramp generator (output = input)
m
Optional interpolation of the ramp function generator set value input (see chapter
For correct functioning of the braking procedures on the Quick Stop or Ramp-down
ramps, the speed controller must be adequately configured.
Trapezoidal Pro-
file
The ramp-up and ramp-down times refer to a change in the input set value of +100% or
-100%.
The resulting times for other set value changes are calculated as follows:
T
ResRamp-up
= T
Ramp-up
* Set value change / 100 %
T
ResRamp-down
= T
Ramp-down
* Set value change / 100 %