Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
247
3
150.18
Status PID controller 2
Status of the PID controller:
150.19
Axis index PID controller 2
Index to select the axis from which the PID controller 2 reads the set value and the actual
value and and on which the PID controller writes the output.
150.20
Source number set value PID controller 2
Selection of the source of the PID controller set value. At source number = 0 the value
can be specified directly, e.g. via a fieldbus or an analogous input.
150.21
Source number actual value PID controller 2
Selection of the source of the PID controller actual value. At source number = 0 the value
can be specified directly, e.g. via a fieldbus or an analogous input.
Bit
Meaning
0
0: PID controller is deactivated
1: PID controller is activated
3 ... 1
Reserved
4
1: PID controller output is limited
7 ... 5
Reserved
8
If PID controller output is linked only (
0):
1: PID controller output greater than maximum value or less than minimum
value of the target parameter. PID controller output is limited to target
parameter at writing.
9
If PID controller input is linked only (
0 or
0):
1: PID controller source number set value or actual value is greater than
maximum value or less than minimum value of the set value or actual
value. PID controller source number set value or actual value is limited to
set value or actual value at writing.
15 ... 10 Reserved
Value
Meaning
0
Assign PID controller to axis 1
1
Assign PID controller to axis 2
65535 ... 2 Reserved