![Baumuller b maXX BM5800 Parameter Manual Download Page 218](http://html.mh-extra.com/html/baumuller/b-maxx-bm5800/b-maxx-bm5800_parameter-manual_2711380218.webp)
Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
218
3.4
The transmission occurs in line with a controller interrupt. The time is set in a grid of con-
troller cycles (62.5 µs).
A setting of 0 controller cycles means that the actual values are transmitted in the inter-
rupt in which the fieldbus task is started in the following. In this way the reading of the set
values follow close upon the transmission of the actual values due to this setting.
131.24
Profinet device name
This parameter contains the Profinet device name (max. 240 characters). ProDrive dis-
plays this parameter as text on the Configuration / Fieldbus slave page, if the fieldbus of
the connected controller is a Profinet type.
131.25
IP address service interface
IP address for the separate service interface (connector X1, optional).
The service interface always has the IP address 192.168.0.1, an additional IP address
can also be specified, where the drive can be reached via the service interface, as well.
The change of this IP address is accepted at the next booting, only.
Example:
IP address fieldbus (e.g. EtherCAT):
192.168.a.x
IP address service interface:
192.168.b.y
The following must apply: a
b and a
0 and b
0.
131.52
Error counter fieldbus actual values
Error counter for access conflicts at actual values.
The counter is incremented, if the fieldbus firmware did not retrieve the actual values. If
the fieldbus is in operational state and the drive is synchronous with the fieldbus, the error
1937 is set at exceeding of threshold
.
NOTE!
The IP address of the fieldbus interface (for the tunneling of Ethernet connections)
and the service interface may not be in the same subnet. The subnet mask of the ser-
vice interface is permanently set to 255.255.255.0. If this IP address is in the same
subnet, the drive cannot be reached via the tunneling!
This applies as well, if the service interface is not assembled!
Furthermore, the IP address set in the parameter
>
131.25
<
is not to be in the subnet
192.168.0.x.