Set Standard Values for an Individual Data Set
This data set command resets all parameter of the target data set (the data set parameter
only) to the default values.
Possible error messages:
n
Device is not inhibited
3.5.2.10 Changeover to Data Set 1 to 7
Changing data sets is possible both with the device inhibited and with the controller run-
ning.
Due to the mechanical inertia of the systems being controlled and the high sampling rate
of the drive, a changeover free of mechanical shocks can be assumed.
The data set changeover is effected by writing to the Parameter
Active Data Set
Number.
Before the changeover, a check is made to ensure that the data set has been created.
3.5.2.11 Overview of the Data Set Management Commands
NOTE!
No consideration can be given to inconsistent set values and monitored values during
the changeover of data sets. During the changeover, the possibility cannot be ruled
out that, e.g., a monitored value in the new data set is smaller than the associated
instantaneous actual value of the previously active data set. In this case a monitoring
function which, e.g., initiates a pulse inhibit could respond.
Data Set Management
Command
Valu
e
Source data set
Target Data Set
Reset the Data Set Management Sys-
tem
0
Write all parameters from the created
data sets into Flash memory
1
Read Flash completely
2
Clear Flash completely
3
Set standard values for the target data
set
4
Data set which is to
be set to standard
values
Set standard values for all writable
parameters
5