Diagnosis
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
698
3.10
104.7
FFT mode
This parameter is used to set the FFT mode. The mode is used to configure the internal
signal generator.
The parameter 104.7 FFT mode is independent from Parameter
Command.
104.8
FFT info
This parameter shows the current information/error of the module.
FFT Mode
Meaning
Value 0
Signal generator not active, default setting
Bit 1 set (0x02) Hissing noise signal generator (15 Bit) active
Bit 3 ... 2
Reserved
Bit 4 set (0x10) Sine generator active
Bit 5 set (0x20) PRBS signal generator active
Bit 6 set (0x40) Hissing noise signal generator (31 Bit) active
Bit 32 ... 7
Reserved
Value
Meaning
0
No error
1
Internal memory for Vector 1 could not be allocated, e.g. due to configured
ring buffer
2
Internal memory for Vector 2 could not be allocated, e.g. due to configured
ring buffer
3
Internal memory for Vector 3 could not be allocated, e.g. due to configured
ring buffer
4
Error wrong command or FFT was interrupted
5
The input parameter configured in Parameter
"Signal input 1
source Pxxx" cannot be read.
6
The input parameter configured in Parameter
"Signal input 2
source Pxxx" cannot be read.
10
Error while reading out the determined curve through Parameter
12
The number of measured values
was indicated outside of the per-
mitted range.