Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
313
3
This parameter defines the response of the drive to a Quick Stop request (by control word
command or hardware control input).
For correct functioning of the braking procedures on the Quick Stop or Ramp-down
ramps, the speed controller must be adequately configured.
108.14
SHUTDOWN reaction code
This parameter is only relevant for axis units.
This parameter defines the response of the drive during the transition from the OPERA-
TION ENABLED to the READY TO SWITCH ON state in the state machine for the device
controller.
For correct functioning of the braking procedures on the Quick Stop or Ramp-down
ramps, the speed controller must be adequately configured.
7
Return to current limit and remain in Quick Stop active mode (renewed
enabling possible)
8
Return to voltage limit and remain in Quick Stop active mode (renewed
enabling possible)
Value
Meaning
NOTICE!
Do not use return to current limit or return to voltage limit during U/f operation
Value
Meaning
0
Inhibit drive immediately
1
Return to ramp-down ramp
2
Return to Quick Stop ramp
3
Return to current limit
NOTICE!
Do not use return to current limit during U/f operation