Set Value Generators
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
356
3.6
T
Ramp up
= Ramp-up time
T
HSK
T
Ramp down
T
HSK
= S-Curve ramp-down time
Figure 89:
Ramp Function Generator S-Curve Profile
The equations apply only to a set value change from standstill (Set value = 0%; Acceler-
ation = 0).
For set value changes less than 100%, two cases for determining the resulting ramp-up
and ramp-down times must be distinguished:
n
the maximum acceleration or deceleration is achieved
n
the maximum acceleration or deceleration is not achieved
In the following, the calculation of the resulting ramp-up time for the two cases is ex-
plained by means of examples for the ramp-up.
The calculation of a resulting ramp-down time would be performed in the same way using
the parameters
Ramp-down Time and
S-Curve Ramp-down Time.