Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
345
3
100.5
First error
The parameter shows the error number of the first error, which leads to a drive reaction.
When acknowledging the error, the parameter is deleted again.
100.7
Error communication mode
Configuration of the error communication between two drives.
By means of the error communication two drives could respond to the errors of the other
in each case if an error reaction was parameterized, i.e.
of the correspondent
error
-1, -2.
Default: 0
100.8
Error reaction actual value
Error code sent to the other drive in the event of an error if
bit 0 = 1 and bit 1 = 1.
At external transmission (fieldbus) the parameter must be mapped cyclically so that it ap-
pears as an actual value on the sending drive and as a set value on the receiving drive.
I.e. the control must copy
of drive 1 to
of drive 2.
At internal transmission this parameter is displayed for diagnostics.
100.9
Error reaction set value
This error code is sent from the other drive. The receiving drive should execute this reac-
tion, if
bit 0 = 1 and bit 1 = 1.
At external transmission (fieldbus) the parameter must be mapped cyclically so that it ap-
pears as an actual value on the sending drive and as a set value on the receiving drive.
I.e. the control must copy
of drive 1 to
of drive 2.
Bit
Meaning
0
0: Switch off error communication
1: Switch on error communication
1
Transmission path
0: external
Error reactions are transferred via fieldbus
1: internal
Values are transferred from axis to axis without external connection. This
is only possible at double axes.
CAUTION:
At double axes the value of bit 1 must be the same for BOTH axes!
15 … 2
Reserved