Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
71
3
130.9
Fan mode
Reserved
130.10
Mode
Settings for the mains rectifier unit.
The parameter is changeable only in locked status.
Bit 1:
At mains failure a motorized operation is advisable, if there is enough energy in the DC
link or if several axes are coupled via the DC link and simultaneously at the other axis
energy is supplied to the DC link.
The setting for the behavior at mains failure effects only in the set time in
. If the
time is set to 0, the drive is inhibited at once at mains failure and an accordant error mes-
sage is generated (error 1016 Mains failure or error 1032 Error DC-link supply).
Bit #
Meaning
0
Reserved
1
Behavior at mains failure:
0: The motorized operation is inhibited at mains failure
1: Motorized operation is possible if there is a mains failure
2
0: Limitation of the motor current to
Current phase error; no
shutdown
1: Limitation of the motor current to
of the drive after the duration in
Phase error delay time
4 ... 3
Reserved
5
Automatic restart after mains failure:
0: At mains failure the drive remains enabled for the time set in
Mains failure delay. According to the setting of bit 1 the motor operation
is disabled internally.
1: At mains failure the pulses are inhibited at once and the drive changes
in the "Switch-on inhibit" state. If mains is available again within the set
time in
, the drive is enabled automatically (automatic restart).
It is essential generally: If the mains failure is longer than the set time in
an error message is generated.
6
Switches off the ground current monitoring:
Ground current measured:
Maximum ground current:
If the measured ground current is greater than
pulse inhibit
results when ground current monitoring is activated.
0: Ground current monitoring active
1: No ground current monitoring
15 ... 7
Reserved