3.5.3.5 Description of the Parameters
134.1
Mode
Triggering the motor holding brake
Bit
Meaning
0
Operating mode
0:
Manual operation
1:
Automatic
1
Polarity of brake actuation signal
0:
Enable brake with control input = low
1:
Enable brake with control input = high
2
Control signal:
0: Standard
(BM5200/5300: Controller output X207/X208)
(BM5400/5500: Power unit output X101)
1: Alternative
(BM5200/5300: Digital output X2)
(BM5400/5500: Digital output X2)
If a digital output is needed, the special function „Triggering holding brake“
must be selected at the digital outputs.
3
Reserved
4
Brake state monitoring
0:
Switch off
1:
Switch on
5
Polarity of brake state signal
0:
Brake is enabled when response signal = low
1:
Brake is enabled when response signal = high
6
Feedback signal brake status:
0: Standard
(BM5200/5300: Controller input X207/X208)
(BM5400/5500: Power unit output X101)
1: Digital input
(BM5200/5300: Digital input X2)
(BM5400/5500: Digital input X2)
If a digital input is needed, the special function „Feedback holding brake“
must be selected at the digital inputs.
10 ... 7
Reserved
11
Watchdog for brake monitoring at an opened brake
0:
Switch off
1:
Switch on
31 ... 12
Reserved