Mode of Iq limit
The mode of the torque current limit will be set with this parameter.
Bit 0
:
Bit no.
Meaning
0
0: for motor/generator (default)
1: for instantaneous direction 1 / instantaneous direction 2
1
Bit mode
maximum torque current
reference variable
(for the ASM, only).
(relevant only if
138.1
bit 3 = 0)
Mode bit to calculate the "Max. torque current"
Increase of the "Max. torque current "
at field weakening by calcu-
lation of the parameter with the "Isd set value"
instead of "Max.
field current amplitude"
0: activated
1: deactivated
2
Breakdown torque limit:
0: deactivated
1: activated (at asynchronous machines always)
(also see bit 5)
3
Additional bit mode: Max. torque current reference value
Additional mode to calculate the "Max. torque current"
:
0: Load mode (standard setting)
1: Current mode
4
Breakdown torque controller
0: deactivated
1: activated
If the breakdown torque controller was activated then the breakdown
torque limit is not effective anymore!
5
Adapting the breakdown torque limit
0: activated
1: deactivated
(if breakdown torque limit is activated, only, refer to bit 2)
15 ... 6
Reserved