Error descriptions
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
736
4.5
402
Error while initializing the position
through Sin/Cos signals.
Error while initializing the position (the analogous signals do not
agree with the position which was digital read out).
Pulse block
403
Encoder monitoring: Overspeed due to
sector error
Sector error occurred while the encoder evaluation, which means
the calculated speed is too great
Pulse block
404
Signal monitoring at square-wave
incremental encoder
The signal monitoring of a square-wave incremental encoder has
recognized an error.
Pulse block
405
CRC error in received data
CRC error in received data from EnDat
2.1, HIPERFACE DSL
or
SSI
Pulse block
406
Lighting failure EnDat
interface
The error is triggered by module EnDat
interface when the abso-
lute encoder reports a lighting failure via the EnDat
interface. With-
out lighting, the optical sampling system of the encoder no longer
works and no valid position information can be calculated anymore.
m
Cause:
Cause for a lighting failure in the encoder may be contamination,
aging, or excess temperature.
n
Remedy:
Replace encoder.
Pulse block
407
Signal amplitude too small EnDat
interface
The error is triggered by the module EnDat
interface when the
absolute encoder reports via the EnDat
interface that the ampli-
tude of the Sine/Cosine signals is too small. Sine/Cosine signals that
are too small can lead to a position loss.
m
Cause:
Cause for sine/cosine signals that are too small may be contami-
nation, aging, or excess temperature.
n
Remedy:
Replace encoder.
Pulse block
408
Position error EnDat
interface
The error is triggered by the module EnDat
interface when an error
occurred during the calculation of the absolute position in the abso-
lute encoder. An incorrect absolute position can lead to miscommu-
nication for synchronous motors.
m
Cause:
Cause for an incorrect position calculation may be contamination,
aging, or excess temperature.
n
Remedy:
Replace encoder.
Pulse block
409
Overvoltage EnDat
interface
The error is triggered by the module EnDat
interface when the
absolute absolute encoder reports via the EnDat
interface that the
supply voltage applied to the encoder is too high.
m
Cause:
Cause for supply voltage applied to the encoder may be a defec-
tive Sense line (Pin12 on X24/X25, Sub-D15). In this case, the
supply voltage may be switched to 8 V (Stegmann encoder).
n
Remedy:
Check encoder cable
m
Cause:
Cause can also be a defect in the encoder hardware.
n
Remedy:
Replace encoder.
Pulse block
Error
num-
ber
Brief error text
Error description
Default set-
ting for
Error
Response