Error descriptions
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
746
4.5
1024
Current offset error
The error will be triggered when the measured current offset is
greater than 5% of the possible measuring range of the AD con-
verter. Only one phase must thereby indicate this error.
Pulse block
1025
Setting of pulse enable (IF) and PWM
not synchronous with DSP
The error is triggered when the PWM counter is no longer synchro-
nous with the DSP Interrupt system and the pulse activation has
been enabled.
Pulse block
1027
Mains feed in detected but DC feed in
configured
Pulse block
1032
Error DC-link supply
DC-link undervoltage detected (see
) or signal "supply
ready for use" of the Signal Bus is low.
Pulse block
1033
Signal bus line warning active
Signal bus line "Warning" is active
No response
1035
No valid Lt data available in the One
Wire Eeprom
Warning: No valid Lt data available in the One Wire EEPROM.
m
Effect:
The parameterization of the power unit parameters occurs from
the data record or it is faulty.
Pulse block
1037
Signal error during communication with
the One Wire EEprom
Signal error during communication with the One Wire EEPROM
m
Effect:
Communication with the One Wire EEPROM is faulty. The power
unit data could not be read out. The power unit could thereby not
be parameterized.
Pulse block
1038
No Lt One Wire EEProm
Warning: No Lt Data One Wire EEPROM exists!
Pulse block
1039
reserved
reserved
No response
1040
reserved
reserved
No response
1041
reserved
reserved
No response
1042
reserved
reserved
No response
1043
Warning: Undervoltage DC link voltage Warning: Undervoltage DC link voltage
No response
1046
Warning: Deactivation through safety
technology
The safety function Safe Torque Off is active
No response
1048
Warning: Mains failure / Supply not
ready
A mains failure was detected or the supply is not ready-to-operate.
The warning is triggered independent of the drive state. If the drive is
enabled, the error 1016 (Mains failure) or 1032 (Error DC-link sup-
ply) is generated at the end of the Mains failure delay.
Further details see
Mains failure delay
No response
1049
Temperature warning threshold heat
sink exceeded
Temperature warning threshold heat sink exceeded
No response
1050
Temperature warning threshold Inside
Air exceeded
No response
1054
DSP Timeout Error: DSP does not
write the PWM Pot Registers in time, 3
times within 100 ms
DSP Timeout Error: DSP does not write the PWM Pot Registers in
time, 3 times within 100 ms
Pulse block
1056
Performance element 24 V Fail
When the 24V supply voltage drops below a specific threshold the
FPGA will activate a corresponding error bit in its status and block
the pulses.
m
Effect:
The response from the related DSP error message must neces-
sarily the pulse block so that the drive manager and thereby the
control loops remain synchronous with the status of the pulse
enable.
Pulse block
1057
15 V faul - power cycle required
The 15 V power supply failed.
Pulse block
1069
Temperature model data inconsistent
Pulse block
Error
num-
ber
Brief error text
Error description
Default set-
ting for
Error
Response