Set Value Generators
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
368
3.6
110.3
Output
Output value of the ramp function generator.
Standardization:
100%
=
Maximum drive speed (
, [rpm])
The output value of the ramp function generator is written to the input of the set value
manager (chapter
). For this purpose the value must be converted from the 100%
standardization to 32-bit increments/revolution per sensing.
The permitted range of the set value manager input is ± (2
31
-1) increments per sensing.
If the converted ramp function generator exceeds this range it is limited and the error 910
"Overspeed detected at the set value input".
At the standard sensing time of the ramp function generator of 1 ms the permitted set val-
ue range ± 29999 rpm. If the ramp function generator is operating in the fieldbus task
(
Mode bit 16 = 1), its cycle time is set by means of the
Fieldbus cycle
time and the
Division ratio fieldbus task.
Example:
Active cycle time ramp generator = 500 µs
Set value range ± 59999 rpm
Active cycle time ramp generator = 2000 µs
Set value range ± 14999 rpm
110.4
Input 32-bit
Ramp generator input value with 32-bit resolution. This input is activated instead of the
16-bit input by means of
Ramp function generator mode bit 5 = 0.
Standardization:
100%
=
Maximum drive speed (
, [rpm])
110.5
Input 16-bit
Ramp generator input value with 16-bit resolution. This input is activated instead of the
32-bit input by means of
Ramp function generator mode Bit 5 = 1.
Standardization:
100%
=
Maximum drive speed (
, [rpm])
110.6
Ramp-up time
Acceleration ramp for the speed-controlled operating modes.
The time selected here applies to a 100% set value change