Set Value Generators
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
370
3.6
110.11
Smoothing
A PT
1
element is implemented to achieve rounding of the ramp corners. The time con-
stant of the PT
1
element can be adjusted using this parameter.
The smoothing is only effective if a trapezoidal profile is set for the ramp shape.
The smoothing is also active if the ramp times (
Ramp-down time) are set to zero.
110.12
Set value zone
This parameter defines the reporting threshold for the ramp function generator status
(bit 12) "Set value reached".
The "Set value reached" status bit is set if the following is valid:
FG
Output
- HLG
Input
Set value zone
110.13
Maximum drive speed
This parameter defines the speed standardization for the ramp generator inputs, the ramp
generator output and the input value limits.
100% (
Input 32-bit)
=
Maximum drive speed [rpm]
100% (
Input 16-bit)
=
Maximum drive speed [rpm]
A change of this parameter affects only if the ramp function generator is activated again
or a ramp function generator command is set via
Control word bits 4, 5 or 6.
110.15
Input max. amount
Absolute value of upper limit of the active ramp generator input (
Parameter value with 32-bit resolution.
Standardization:
100%
=
Maximum drive speed (
, [rpm])
CAUTION!
If Maximum drive speed is greater than
Max speed mech., error 212 is set
at drive enabling in the operating modes 2 and -3. Maximum drive speed must set so
that the maximum speed mechanical of the motor cannot be exceeded. If the error is
ignored the speed set value can exceed the maximum speed mechanical and can
lead to damaging the motor or the mechanical setup!
This check of the parameterization doesn’t proceed if in
the value 0 rpm is
set.