4-32 Protection
and
Control BE1-CDS220
Figure 4-28. BESTlogic Function Element Screen, 50BF
At the top center of the
BESTlogic Function Element
Screen is a pull-down menu labeled
Logic
. This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A custom logic
scheme must be created and selected in the
Logic
pull-down menu at the top of the screen before
BESTlogic settings can be changed. See Section 7,
BESTlogic Programmable Logic
.
Enable the breaker failure function by selecting its mode of operation from the
Mode
pull-down menu. To
connect the elements inputs, select the button for the corresponding input in the
BESTlogic Function
Element
Screen. The
BESTlogic Expression Builder
screen will open. Select the expression type to be
used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select
Save
when finished to return to the
BESTlogic Function Element
Screen. For more details on the
BESTlogic Expression Builder
, see Section 7,
BESTlogic Programmable Logic
. Select
Done
when the
settings have been completely edited.
Table 4-17 summarizes the BESTlogic settings for Breaker Failure.
Table 4-17. BESTlogic Settings for Breaker Failure
Function
Range/Purpose Default
Mode
0 = Disable
1 = CT Input Circuit 1
2 = CT Input Circuit 2
0
INI
Logic expression that starts the breaker failure timer when TRUE and current is
flowing in the assigned input circuit.
0
BLK
Logic expression that disables function when TRUE.
0
Example 1.
Make the following changes to the Breaker Failure element. Refer to Figure 4-28.
Mode
:
CT Input 1
INI
:
IN3
BLK
:
IN6
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......