TIME RELAY
- MOTOR START (STAR/DELTA) PCM-08
ZAMEL
Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04
www.zamel.com
, e-mail: [email protected]
plik: inst_ext_gb_pcm-08 | modyfikacja: 30.12.2016
INSTRUCTION
MANUAL
APPEARANCE
FEATURES
TECHNICAL PARAMETERS
DESCRIPTION
● Three-phase delta-star motor control,
● current decrease during high power
motor start,
● device mode optical signalling (LED
red),
● supply voltage optical signalling (LED
green),
● trigger by applying supply voltage,
● starting time adjustment (STAR sys-
tem),
● interval time adjustment of STAR to
DELTA switching,
● two independent relay outputs, dry
contact 2 x NO/NC of 10 A capacity,
● mounting in distribution boards (TH35
rail).
The PCM-08 time relay is used to
control the STAR-DELTA contactor
switch. It is applied in three-phase mo-
tor control systems. This control me-
thod allows to reduce starting currents
in case of motor units with a capacity
of more than 4-5 kW and additionally it
provides safety. The PCM-08 device has
two independent relay outputs activated
according to the settings of P1-P3 po-
tentiometers. It is possible to adjust the
starting time (in the STAR system) and
time interval of star to delta switching.
Relay operation is triggered by applying
power supply voltage to the L, N supply
terminals. The device is designed to be
mounted in distribution boards (TH35
rail). The LEDs on the front panel in-
dicate power supply (LED green), and
device operating mode (LED red).
PCM-08
Power supply terminals: L, N
Nominal supply voltage: 230 V AC
Input voltage tolerance: -15 ÷ +10 %
Nominal frequency: 50 Hz
Nominal power consumption: 0,8 W
Supply voltage control indicator: LED green
Device mode indicator: LED red
Interval time adjustment of STAR to DELTA switching: discreet – 8 ÷ 250 ms
Starting time adjustment (STAR system):
1 ÷ 100 s with multiplier 1÷10
Output elements:
2 x relay
Output relay parameters:
NO/NC – 10 A / 250 VAC
Number of terminal clamps:
8
Cross-section of connecting cables: 0,2 ÷ 2,5 mm
2
Operating temperature range: -20 ÷ +50 °C
Operating position: free
Casing mounting: TH35 rail (1-MOD casing)
Casing protection degree: IP20
Protection level: II
Overvoltage category: II
Pollution degree: 2
Surge voltage: 1 kV (PN-EN 61000-4-5)
Dimensions: monomodular 90x17,5x66 mm
Weight: 0,08 kg
Reference standard: PN-EN 60669-1, PN-EN 60669-2-1,
PN-EN 61000-4-2,3,4,5,6,11
The symbol means selective
collecting of electrical and
electronical equipment. It
is forbidden to put the used
equipment together with other
waste.
P1 potentiometer
Interval time adjustment
of STAR to DELTA switching
(strobe adjustment)
P3 potentiometer
Starting time multiplier
in the star system 1÷10
(strobe adjustment)
P2 potentiometer
starting time value adjustment
(STAR system),
Device operating mode
optical signalling
Power supply optical signalling
Relay output terminals
PK1 (14, 11, 12)
Relay output terminals
PK2 (24, 21, 22)