13-70
Testing And Maintenance
BE1-CDS220
Command Purpose
SN-143=GROUP_MAN_SELECT,
GROUP1,NORMAL
Set Switch Names
SN-243=GROUP_MAN_SELECT,
GROUP2,NORMAL
Set Switch Names
SN-343=GROUP_MAN_SELECT,
GROUP3,NORMAL
Set Switch Names
SN-443=GROUP_CONTROL,
AUTO,MANUAL
Set Switch Names
SP-GROUP1=1,75,1,70,51P SG1
t
s
=1min@75%, t
r
=1min@70% of SG0 51P
SP-GROUP2=1,90,1,85,51P SG2
t
s
=1min@90%, t
r
=1min@85% of SG0 51P
SP-GROUP3=1,110,1,100,51P SG3
t
s
=1min@110%, t
r
=1min@100% of SG0 51P
E Exit
Y Save
settings
Step 3.
Switch group control to automatic using virtual switch 443. Use Table 13-81 ASCII commands
or front panel interface \CTRL\43\543, screen 2.1.6.
Table 13-81. Automatic Group Control Selection
Command Purpose
A= Gain
access
CS-443=1
Selects 443 for TRUE operation
CO-443=1
Executes 443 TRUE operation (AUTO)
Step 4.
Gain access if access timed out from the previous step. Send to the relay the appropriate
setting commands from Table 13-82. If your relay is supplied with the HMI option, you may
also go to the front panel interface screen \PROT\SG0\51\51 and edit the 51P settings. After
you send the commands to your relay, EXIT’ and (save) ‘Y’) the changes.
An ohmmeter or continuity tester may be used to monitor the output contacts (OUT1, OUT2,
and OUT3) status.
Table 13-82. Time Overcurrent 51P Element Pickup Settings
Sensing Input Type
Command Comments
1 A
S0-51P=1.0,5.0,I2
pu=1.0, td=5, curve=I2
S1-51P=1.5,5.0,I2
pu=1.5, td=5, curve=I2
S2-51P=1.8,5.0,I2
pu=1.8, td=5, curve=I2
S3-51P=2.2,5.0,I2
pu=2.2, td=5, curve=I2
5 A
S0-51P=5.0,5.0,I2
pu=5.0, td=5, curve=I2
S1-51P=7.5,5.0,I2
pu=7.5, td=5, curve=I2
S2-51P=9.0,5.0,I2
pu=9.0, td=5, curve=I2
S3-51P=11.0,5.0,I2
pu=10.5, td=5, curve=I2
Step 5.
Using the values listed in Table 13-83, apply current to the A phase current input, beginning at
the starting point, then stepping up to just slightly above the threshold limit for the amount of
time listed. If the active setting group does not change, step the current up to just below the
next group switch limit for the duration indicated. The setting group change should occur
between the low and high limits. Monitor the output contacts to verify that the change occurred
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......