BE1-CDS220
Testing And Maintenance
13-49
circuit
monitor
current
source 1
180 degrees
current
source 2
B1 B3 B5 B7
B2 B4 B6 B8
B9 B11 B13 B15
B10 B12 B14 B16
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
I
A1
I
B1
I
C1
I
G
I
A2
I
B2
I
C2
Figure 13-16. Connection for 87ND Restraint Pickup Verification
Step 2.
To prepare the 87ND element for testing the restraint operation accuracy, transmit the
commands in Table 13-37 to the relay.
Table 13-37. 87ND Restraint Operation Accuracy Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm
overwrite
SL-N=NDIFF
Name custom logic for this test
SL-87=0 Disables
87
SL-87ND=2,0
Enables 87ND, mode=IG v. CT2, no blk
SL-VO1=87NDT
Enables OUT1 to close for 87ND restrained trip
SG-CT2=1,WYE,NA,0
input 2 ctr=1, ct=wye, xfmr=na, no grd source
SG-CTG=1
gnd input ctr=1
SG-TRIGGER=87NDT,
87NDPU,0
Enable 87NDT to log and trigger fault recording
S#-87ND=0.35,15,50m
Minpu = 0.35, slope = 15%, minimum time delay
E Exit
Y Save
settings
NOTE
The ground differential function always uses the maximum restraint principle as its
operating characteristic. Thus, the slope setting is simply a number between 15 and 60.
Step 3.
The auto tap compensation logic of the relay will calculate TAPN and TAPG values based on
CT ratios for the designated phase CTs and the ground CT. Since CTR2 and CTRG are both
equal to 1:1 for this test, the TAPN and TAPG values are both equal to the minimum settings
for either 5 ampere or 1 ampere relays (2.0 and 0.4 respectively).
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......