13-48
Testing And Maintenance
BE1-CDS220
NOTE
With the relay in service, it is necessary to view the 87ND tap factors by accessing the
HMI screen \PROT\SGn\87ND\87ND.
Step 3.
The relay auto tap compensation logic will calculate TAPN and TAPG values based on the CT
ratios for the designated phase CTs and the ground CT. Since CTR2 and CTRG are both
equal to 1:1 for this test, the TAPN and TAPG values are both equal to the minimum settings
for either 5 ampere or 1 ampere relays (2.0 and 0.4 respectively). For more information on auto
tap compensation, see Sidebar 13-9.
Sidebar 13-9. Auto Tap Compensation
Tap adjustment factors for the 87ND function are automatically calculated based on the equation:
TAPN * CTRn = TAPG * CTRG
where CTRn is the CT ratio for the CT designated in the SL-87ND setting in the active logic. Currents are
tap adjusted based on the CT ratios with the driving tap (CT input with the highest CTR) set at the
minimum setting (2.0 for 5 ampere sensing relays and 0.4 for 1 ampere sensing relays) and the other tap
adjusted to the driving tap based on the equation above. For more information on Auto Tap
Compensation, refer to Section 4,
Protection and Control Functions, Differential Protection, 87ND Neutral
Differential Function.
Step 4.
Apply current to the ground input and slowly ramp up until OUT1 closes.
Step 5.
Accuracy when increasing or decreasing the input current is
±
4% of setting or 75 milliamperes
(whichever is larger) for 5 ampere sensing inputs and
±
4% of setting or 25 milliamperes
(whichever is larger) for 1 ampere sensing inputs. Verify that pickup occurred within the
specified accuracy of the relay.
Step 6.
Decrease the current to the ground input until the relay drops out.
Step 7.
Repeat for all other values shown in Table 13-36 by substituting for minpu in the S#-87ND
command or if supplied with the HMI option, by navigating to screen \PROT\SGn\87ND\87ND
and editing the MIN PICKUP value.
Table 13-36. Minimum Pickup Accuracy Limits (87ND)
Sensing Type MINPU Calculated TAPG
Pickup (A)
Low Limit (A)
High Limit (A)
5 A
0.10
2.00
0.20
0.125
0.275
0.50
2.00 1.00
0.925
1.075
1.00
2.00 2.00
1.920
2.080
1 A
0.10
0.40
0.04
0.015
0.065
0.50
0.40 0.20
0.175
0.225
1.00
0.40 0.40
0.375
0.425
Step 8.
(Optional) Repeat Steps 2 through 8 for setting groups 1 through 3, using the CS/CO-GROUP
command to change setting groups.
Restrained Pickup Verification (87ND)
Purpose:
To verify the accuracy of the restraint operation of the 87ND element.
Reference Commands:
SL-87ND, SL- VO, SG-CT, S(n)-87, S(n)-TAP87
Step 1.
Connect one current source to terminals B9 and B10 (A-phase input 2) and a second source at
180
o
to terminals B7 and B8 (ground input). See Figure 13-16. An ohm-meter or continuity
tester may be used to monitor output contact status.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......