BE1-CDS220
Testing And Maintenance
13-69
Timer T1 timed out and the 62 timer output went TRUE 30 seconds after 43 switch action
(TRUE).
62 timer output returned to a FALSE state with the 143 switch action (TRUE).
200 ms
200 ms
T1
INI
x62
1
1
0
0
D2595-06.vsd
08-10-00
BLK
1
0
~ ~
Figure 13-21. x62 Mode 6 (Latch) Timing Example
Step 4.
(Optional) Repeat the 62 timer tests for Modes 1, 2, 3, and 5 for setting groups 1, 2, and 3.
Automatic Setting Group Change
Automatic Change
Purpose
: To verify the operation of the automatic setting group change function.
Reference Commands
: SL-GROUP, SG-SGCON, SP-GROUP, CS/CO-GROUP, SL-51/151/251,
S<n>-51
Step 1.
Connect a current source to terminals B1 and B2 (A-phase input 1).
Step 2.
To initially prepare the automatic setting group change function for testing, transmit the
commands in Table 13-80 to the relay.
Table 13-80. Automatic Setting Group Change Function Test Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic = none
settings
Y Confirm
overwrite
SL-N=ASG
Name custom logic for this test
SL-GROUP=1,43,143,243,343, 443
Sets logic mode to discrete selection with virtual switches to
control
SL-51P=1,0
Enables 51P CT input 1
SG-SGCON=1
Sets SGC alarm = 1 sec, and anti-pump = 2 sec
SL-VO1=SG1
Enables OUT1 to close when SG1 active
SL-VO2=SG2
Enables OUT2 to close when SG2 active
SL-VO3=SG3
Enables OUT3 to close when SG3 active
SG-CT1=1,WYE,NA,0
Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=51PT,51PPU,0
Enable 51PT to log and trigger fault recording
SL-43=2
Enables 43 switch ON /OFF mode
SL-143=2
Enables 143 switch ON /OFF mode
SL-243=2
Enables 243 switch ON /OFF mode
SL-343=2
Enables 343 switch ON /OFF mode
SL-443=2
Enables 443 switch ON /OFF mode
SN-43=GROUP_MAN_SELECT,
GROUP0,NORMAL
Set Switch Names
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......