12-16 Installation BE1-CDS220
P0001-08
09-21-00
With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or Delta AC). For more information, refer to Section 3, Input And Output
Functions, Input Current.
To cancel out the zero sequence current source inside the zone of protection, connect circuit 2 CTs in
wye and specify a ground source on the delta transformer winding. For more information, refer to
Section 1, General Information, Problem 5.
Phase, Residual, and
I
2
overcurrent elements can be connected to either CT circuit for backup
protection. For more information on applying overcurrent backup, refer to Section 8, Application.
Overcurrent neutral ground (
I
N
) operates on internally calculated residual (3I0) current.
For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
System with the BE1-CDS220 (refer to Figure 12-18 for a connection diagram). To add only metering to
the BE1-CDS220, connect a BE1-MMS100.
1
2
3
1
BE1-CDS220
B2
B5
B1
B3
B6
B4
I
C1
I
B1
I
A1
1
B10
B14
B12
B9
I
A2
I
B2
I
C2
B13
B11
3
2
4
H1
H2
H3
X1
X2
X3
DAC
Groundin
g Bank
3I0
4
3
4
5
Low Side Breaker
AØ
BØ
CØ
Figure 12-19. Differential Protection for Wye-Grounded-Delta Transformer
with Ground Source inside the Protected Zone
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......