BE1-CDS220
Time Overcurrent Characteristic Curves
A-3
Table A-2. Characteristic Curve Cross-Reference
Curve Curve
Name
Drawing No.
Similar To
S1
S, S1, Short Inverse
99-1369
ABB CO-2
S2
S2, Short Inverse
99-1595
GE IAC-55
L1
L, L1, Long Inverse
99-1370
ABB CO-5
L2
L2, Long Inverse
99-1594
GE IAC-66
D
D, Definite Time
99-1371
ABB CO-6
M
M, Moderately Inverse
99-1372
ABB CO-7
I1
I, I1, Inverse Time
99-1373
ABB CO-8
I2
I2, Inverse Time
99-1597
GE IAC-51
V1
V, V1, Very Inverse
99-1374
ABB CO-9
V2
V2, Very Inverse
99-1596
GE IAC-53
E1
E, E1, Extremely Inverse
99-1375
ABB CO-11
E2
E2, Extremely Inverse
99-1598
GE IAC-77
A
A, Standard Inverse
99-1621
BS, IEC Standard Inverse
B
B, Very Inverse (I
2
t)
99-1376
BS, IEC Very Inverse (I
2
t)
C
C, Extremely Inverse (I
2
t)
99-1377
BS, IEC Extremely Inverse (I
2
t)
G
G, Long Time Inverse (I
2
t)
99-1622
BS, IEC Long Time Inverse (I
2
t)
F
Fixed Time
N/A
N/A
P
Programmable N/A
N/A
Time Dial Setting Cross-Reference
Although the time characteristic curve shapes have been optimized for each relay, time dial settings of
Basler Electric relays are not identical to the settings of electromechanical induction disk overcurrent
relays. Table A-3 helps you convert the time dial settings of induction disk relays to the equivalent setting
for Basler Electric relays. Enter time dial settings using BESTCOMS, S<g>-
51P/51N/51Q/151P/151N/151Q/251P/251N/251Q ASCII commands, or human-machine interface (HMI)
Screens 5.x.4.1 (51P/N/Q), 5.x.4.2 (151P/N/Q), and 5.x.4.3 (251P/N/Q). For more information, refer to
Section 4, Protection and Control, Overcurrent Protection, 51 - Time Overcurrent Protection.
Using Table A-3
Cross-reference table values were obtained by inspection of published electromechanical time current
characteristic curves. The time delay for a current of five times tap was entered into the time dial calculator
function for each time dial setting. The equivalent Basler Electric time dial setting was then entered into
the cross-reference table.
If your electromechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electromechanical setting
and the Basler Electric setting.
Basler Electric relays have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial
setting for the electromechanical maximum setting is provided in the cross-reference table even if it
exceeds 9.9. This allows interpolation as noted above.
Basler Electric time current characteristics are determined by a linear mathematical equation. The
induction disk of an electromechanical relay has a certain degree of non linearity due to inertial and friction
effects. For this reason, even though every effort has been made to provide characteristic curves with
minimum deviation from the published electromechanical curves, slight deviations can exist between
them.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......