BE1-CDS220 Quick
Start
2-5
R
REPORTS. Read and reset reporting functions such as time and date, demand registers, breaker
duty statistics, etc. Sub-groupings include: A for Alarm functions, B for Breaker monitoring functions,
D for Demand recording functions, F for Fault summary reporting functions, G for General
information and S for Sequence of Events recorder functions.
S
SETTINGS. Set all setting parameters that govern the functioning of the relay. Sub-groupings
include: 0,1,2,3 for settings in setting groups, A for alarm settings, B for breaker monitoring settings,
G for general settings, L for logic settings.
MISCELLANEOUS. These include Access, Exit, and Help.
Examples of object names would be 51N for the neutral inverse time overcurrent element or PIA for the A
phase, peak current demand register.
For example, to check the 51N pickup setting in Setting Group 3, you would enter S3-51N for Settings,
Group 3-51N. The relay would respond with the current pickup, time dial, and curve settings for the 51N
element. To edit these settings, the same command would be used with an = followed by the new settings
and the enter pushbutton. The user should note that it is necessary to use the Access and Exit
commands when using the write version of these commands.
Human-to-Machine ASCII Command Operations
The ASCII command scheme allows the user to read and/or write settings and operational items on a
function-by-function basis. However, this also requires a great many commands. The mnemonic format of
the commands is designed to facilitate interactive communications with the relay. It is not necessary to
remember all of the object names. Most commands support a multiple read version where it is not
necessary to specify a complete object name. You can enter the first two letters of a command and the
relay will respond with all applicable objects.
For example, you want the relay to report the breaker operations counter reading. You can enter RB for
Report Breaker and the relay will respond with all of the breaker report objects including the operations
counter. If you had remembered that the object name is OPCNTR, you could have entered RB-OPCNTR
and received only the operations counter report. Partial object names are also supported. For example,
you wish to read the entire peak-since-reset demand registers. You can enter RD-PI for Report Demand -
Peak Current (I) and the relay will respond with the values and time stamps for A, B, C, N and Q. To reset
all five of the peak since reset demand registers, enter the command RD-PI=0. To read only the value for
the neutral demand, the full object name would have been entered (RD-PIN).
Batch Command Text File Operations
With a few exceptions, each function of the relay uses one command to set it and each setting command
operates on all of the parameters required by that element. See the example mentioned above in the
paragraph titled Command Structure. This format results in a great many commands to fully set the relay.
Also, the process of setting the relay does not use a prompting mode where the relay prompts you for
each parameter in turn until you exit the setting process. For these reasons, a method for setting the relay
using batch text files is recommended.
In batch upload type operations, the user creates an ASCII text file of commands and sends it to the
relay. To facilitate this process, the response from a multiple read command is output from the BE1-
CDS220 in command format. So the user need only enter S for Set (with no subgroup) and the relay
responds with all of the setting commands and their associated parameters. If the user enters S2 for Set
Group 2, the relay responds with all of the setting commands for Setting Group 2. The user may capture
this response to a file, edit it using any ASCII text editor, and then send the file back to the relay. See
Section 11, ASCII Command Interface, for a more detailed discussion of how to use ASCII text files for
setting the relay.
BESTCOMS for BE1-CDS220, Graphical User Interface
Basler Electric's graphical user interface (GUI) software, BESTCOMS, is an alternative method for quickly
developing setting files in a friendly, Windows
based environment. Using the GUI, you may prepare
setting files off-line (without being connected to the relay) and then upload the settings to the relay at your
convenience. These settings include protection and control, operational and logic, breaker and
transformer monitoring, metering and fault recording. Engineering personnel can develop, test, and
replicate the settings before exporting it to a file and transmitting the file to technical personnel in the field.
On the field end, the technician simply imports the file into the BESTCOMS database and uploads the file
to the relay where it is stored in nonvolatile memory.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......