3-12
Input And Output Functions
BE1-CDS220
The hold timer can be enabled for each input from the ASCII command input using the SG-HOLD (setting
general, hold) command. The settings are shown in Table 3-5.
To enable the hold timer using BESTCOMS, select Inputs and Outputs from the Screens pull-down menu,
and select the Outputs 1-6, A tab. To enable the hold timer for a desired output, check the box labeled
Hold Attribute by clicking in the box with the mouse pointer. Refer to Figure 3-8.
Figure 3-8. Inputs and Outputs Screen, Outputs 1-6, A Tab
Table 3-5 lists the default setting for the hold timer attributes.
Table 3-5. Output Hold Function Settings
Setting Range Default
Output Hold Timer
0 = disabled
1 = enabled
OUTA, OUT6 = 0
OUT1 - OUT5 = 1
Output Logic Override Control
The state of each output contact can be controlled directly using the select before operate, output control
function. The virtual output logic expression that normally controls the state of an output contact can be
overridden and the contact pulsed, held open, or held closed. This function is useful for testing purposes.
An alarm point is available in the programmable alarm function for monitoring when the output logic has
been overridden. See Section 6, Reporting and Alarm Functions, Alarms Function for more information on
programmable alarms. Write access to control functions is required to use the select before operate
control functions from either the optional HMI or the ASCII command interface. It cannot be achieved
using BESTCOMS.
Enabling Logic Override Control
The logic override control must be enabled before the function can be used. The default state is disabled.
Enabling output logic override control cannot be accessed from the HMI. It can only be accessed from the
ASCII command interface using the CS/CO-OUT=ena/dis (control select/control operate-output
override=enable or disable) command. This command only enables or disables logic override control. It
does not enable or disable the outputs themselves.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......