BE1-CDS220
Testing And Maintenance
13-45
Step 1.
Connect one current source to terminals B1, B2 (A-phase, input 1). Refer to Figure 13-1.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2.
Send the commands listed in Table 13-31 to the relay to setup a test of the pickup of the 87
elements.
Table 13-31. 87 Elements Pickup Setup Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm
overwrite
SL-N=UDIFF
Name custom logic for this test
SL-87=1,0 Enables
87
SL-VO1=87UT
Enables OUT1 to close with 87 unrestrained trip
SL-VO2=5THHAR
Enables OUT2 to close when 5
th
harmonic restrains
87RT
SG-CT1=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87UT,87UT,0
Enable 87UT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
S#-87=0,15,0,0,1,1
Minpu = disabled, slope = 15%, 2
nd
= disabled, 5
th
=
disabled, URO = disabled, 2
nd
harm sharing = shared
E Exit
Y Save
settings
Step 3.
Apply current to A-phase input 1, increasing the magnitude until OUT1 closes. Since the URO
setting is 1 and Tap 1= 2, this should occur at 2 amperes. Accuracy when increasing or
decreasing the input current is
±
4% of setting or 75 milliamperes (whichever is larger) for 5
ampere sensing inputs and
±
4% of setting or 25 milliamperes (whichever is larger) for 1
ampere sensing inputs. Verify that pickup occurred within the specified accuracy of the relay.
Step 4.
Reduce the input current until OUT1 opens.
Step 5.
Using the values in Table 13-32, repeat Step 3 for the other values of unrestrained settings
indicated.
Table 13-32. Unrestrained Pickup Accuracy Limits
URO Setting
Tap 1
Pickup (A)
Low Limit (A)
High Limit (A)
1 2.00 2 1.925 2.075
5 2.00
10 9.700 10.30
10 2.00 20 19.40 20.60
Step 6.
(Optional) Repeat steps 1 through 5 for phases B and C.
Step 7.
(Optional) Repeat Steps 2 through 6 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
Unrestrained Time Verification
A timing circuit or a contact monitor with timing algorithm must be used to time the output contact status
change. For more information on determining the minimum pickup current, refer to Sidebar 13-8.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......