BE1-CDS220 Protection
and
Control
4-43
Figure 4-44. BESTlogic Function Element Screen, 101
At the top center of the
BESTlogic Function Element
screen is a pull-down menu labeled
Logic.
This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A custom logic
scheme must be created and selected in the
Logic
pull-down menu at the top of the screen before
BESTlogic settings can be changed. See Section 7,
BESTlogic Programmable Logic
.
Enable the 101 Virtual Breaker Control function by selecting its mode of operation from the
Mode
pull-
down menu. Select
Done
when the settings have been completely edited.
Table 4-22 summarizes the BESTlogic settings for the Virtual Breaker Control Switch.
Table 4-22. BESTlogic Settings for the Virtual Breaker Control Switch
Function Range/Purpose Default
Mode
0 = Disable, 1 = Enable
0
Select Before Operate Control of the Virtual Breaker Control Switch
The state of the virtual breaker control switch can be controlled at the optional HMI through Screens 2.2,
\CTRL\BKR. Control is also possible through the ASCII command interface by using the select-before-
operate commands CS-101 (control select-virtual control switch) and CO-101 (control operate-virtual
control switch). Control is not possible using BESTCOMS. A state change takes place immediately
without having to execute an
Exit - Save
settings command.
CS/CO-101
Command
Purpose:
Select and operate the virtual control switch.
Syntax:
CS/CO-101[=<Action>]
Comments:
Action = T to pulse the 101T output; C to pulse the 101C output
The virtual switch control commands require the use of select-before-operate logic. First, the command
must be selected using the CS-x101 command. After the select command is entered, the CO-101 control
command will be accepted during a 30-second window. The control selected and the operation selected
must match exactly or the operate command will be blocked. If the operate command is blocked and error
message is output.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......