13-72
Testing And Maintenance
BE1-CDS220
Current Value
Sensing
Type
Below Switch
Timing
Threshold
But Above Next
Group Switch
Threshold
Time
Comments
5 A
10.78 A
5.61 A
> 1 min SG3 (110% SG0 51P)
4.9 A
4.4 A
> 1 min Switch to SG2 (100% SG0 51P)
4.16 A
3.57 A
> 1 min Switch to SG1 (85% S0 51P pickup)
3.43 A
2.55 A
> 1 min Switch to SG0 (70% S0 51P pickup)
Step 10.
Remove the current from A-phase, input 1.
Step 11. Using the RS-LGC command to retrieve logic variable data from the SER, verify that the
following actions were logged.
Verify that all setting group changes were logged.
Verify that VO1 went TRUE and closed relay output OUT1 when SG1 became the active
setting group.
Verify that VO2 went TRUE and closed relay output OUT2 when SG2 became the active
setting group and that relay output OUT1 opened.
Verify that VO3 went TRUE and closed relay output OUT3 when SG3 became the active
setting group and that relay output OUT2 opened.
Verify that when the virtual switch 143 went TRUE (as a discrete input to the SG1 input of the
setting group logic block) that the active setting group remained SG3.
Verify the events that occurred in reverse order, when the current was being stepped down.
Manual Change Mode 1
Manual Change Mode 1 test procedures are a continuation of the automatic test procedures. Do not
change the logic or settings except for those in Step 1 and subsequent.
Step 1.
Transmit to the relay the commands in Table 13-86.
Table 13-86. Manual Group Control Selection
Command Purpose
A= Gain
access
CS-443=0
Selects 443 for FALSE operation to enable logic
control (manual mode)
CO-443=0
Executes 443 for FALSE operation to enable logic
control (manual mode)
E Exit
Step 2.
Verify that VO1 went TRUE and closed relay output OUT1 when SG1 became the active
setting group (remember in Step 6, switch 143 was made TRUE).
Step 3.
Send to the relay the commands in Table 13-87. Monitor the output contacts to verify the
setting group changes. After all commands have been sent, verify that SG3 is the active setting
group by sending the command RG-GRPACTIVE to the relay. It should echo back that the
SG3 is the active group. If your relay is supplied with the HMI option, you may also verify the
active setting group at the front panel interface screen \STAT\OPER\ACTIVEG, 1.4.4.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......