13-46
Testing And Maintenance
BE1-CDS220
Step 1.
Connect one current source to terminals B1, B2 (A-phase, input 1) and a second current
source to terminals B9, B10 (A-phase, input 2).
Step 2.
Send the commands listed in Table 13-33 to the relay to setup a test of the response time of
the 87 unrestrained elements.
Table 13-33. Unrestrained Element Response Time Setup Commands
Command Purpose
A= Gain
access
SL-N=NONE
Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm
overwrite
SL-N=DIFF
Sets DIFF as custom logic name
SL-87=1,0 Enables
87
SL-VO1=87UT
Enables OUT1 to close with 87 unrestrained trip
SG-CT1=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0
ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87UT,87UT,0
Enable 87UT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,2.00 set tap 1=2.00 and tap 2=2.00
S#-87=0,15,0,0,2,1
Minpu = 0, slope = 15%, 2
nd
= disabled, 5
th
= disabled,
URO = 2 times TAP unrestrained pickup, 2
nd
harm
sharing = shared
E Exit
Y Save
settings
Step 3.
Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
180
o
phase relation to input 1).
Step 4.
To force an unrestrained trip at 1.5 times pickup, you must apply a step change in the current
on input 2 to 8.0 amps. Apply step change in current to input 2 and record the time interval
between the time the step change was initiated to the time OUT1 output contact closes (the
unrestrained trip (87UT)).
Step 5.
Reduce the current to input 2 until OUT1 contact opens.
Step 6.
Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
180
o
phase relation to input 1).
Step 7.
To force an unrestrained trip at 5 times pickup, you must apply a step change in the current on
input 2 to 22 amperes.
Step 8.
Apply step change in current to input 2 and record the time interval between the time the step
change was initiated to the time OUT1 output contact closes (the unrestrained trip (87UT)).
Step 9.
Reduce the current to input 2 until OUT1 contact opens.
Step 10. The time measured in Steps 4 and 8 should be less than those shown in Table 13-34.
Table 13-34. Restrained Trip Operate Times
Function Differential
current
Time
Unrestrained trip
1.5 times pu
Less than 2 cycles
Unrestrained trip
5 times pu
Less than 1 cycle
Step 11.
(Optional) Repeat steps 1 through 10 for phases B and C.
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......