BE1-CDS220
Testing And Maintenance
13-39
Sidebar 13-7. Average Restraint When Decreasing One Input from Balance - Continued
with the minimum trip point established as:
I
1trip min
= I
2balance
- minpu in per unit
where: minpu is the minimum pickup setting
Under test and in-service conditions, the following equations determine whether the relay operates along
the flat minimum pickup or slope of the operating characteristic. If
I
restraint at balance
> minpu x
+
2
/
1
100
/
1
slope
in per unit, use the 1
st
equation, or if
I
restraint at balance
< minpu x
+
2
/
1
100
/
1
slope
in per unit, use the 2
nd
equation.
Step 12.
Send the commands listed in Table 13-23 to the relay.
Table 13-23. Setup Commands
Command Purpose
A= Gain
access
S#-87=0.35,
15A
,0,0,0,1
Minpu = 0.35, slope = 15% (of average restraint),
2
nd
= disabled, 5
th
= disabled, URO= disabled, 2
nd
harm sharing =1 (yes)
E Exit
Y Save
settings
Step 13. Apply balancing current to phase A input 1 and phase A input 2 at the magnitude indicated in
each row of either Table 13-24 (5 ampere sensing) or 13-25 (1 ampere sensing) and slowly
increase phase A input 1 until OUT1 closes. Reference the corresponding table to verify pickup
accuracy.
Table 13-24. Maximum Restraint Pickup Test Points (5 A Sensing Input)
Sensing
Input 1
Input 2
Increasing Input 1
Decreasing Input 2
Input Minimum slope
tap =
2.00
tap =
3.80
From Balance
From Balance
Type
Pickup
(%)
Bal. Input (A)
PU
Bal. Input (A)
PU
Pickup (A)
Pickup (A)
5
0.35
15
2.00 1 3.80 1
2.70
±
0.108 2.47
±
0.099
5
0.35
15
10.00 5 19.00 5
11.62
±
0.465 16.35
±
0.654
5
0.35
30
2.00 1 3.80 1
2.70
±
0.108 2.47
±
0.089
5
0.35
30
10.00 5 19.00 5
13.53
±
0.541 14.04
±
0.562
5
0.35
45
2.00 1 3.80 1
3.16
±
0.126 2.40
±
0.096
5
0.35
45
10.00 5 19.00 5
15.81
±
0.632 12.03
±
0.481
5
0.35
60
2.00 1 3.80 1
3.71
±
0.148 2.04
±
0.096
5
0.35
60
10.00 5 19.00 5
18.57
±
0.743 10.22
±
0.409
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......