4-40 Protection
and
Control BE1-CDS220
is open (logic 0). For the application, you might set the switch label to be 87_CUTOFF (10 characters
maximum). The closed position on the switch might be labeled DISABLD (7 characters maximum) and the
open position might be labeled NORMAL. Section 7,
BESTlogic Programmable Logic
, has more details
about setting user programmable names for programmable logic variables.
BESTlogic Settings for Virtual Selector Switches
BESTlogic settings are made from the
BESTlogic Function Element
screen in BESTCOMS. Figure 4-40
illustrates the BESTCOMS screen used to select BESTlogic settings for the
Virtual Switch
element. To
open the
BESTlogic Function Element
screen for the
Virtual Switch
element, select
Virtual Switches
from
the
Screens
pull-down menu. Then select the
BESTlogic
button for the virtual switch to be edited.
Alternately, settings may be made using SL-x43 ASCII command (where x = blank, 1, 2, 3, 4, 5, 6, or 7).
At the top center of the
BESTlogic Function Element
screen is a pull-down menu labeled
Logic.
This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A custom logic
scheme must be created and selected in the
Logic
pull-down menu at the top of the screen before
BESTlogic settings can be changed. See Section 7,
BESTlogic Programmable Logic
.
Enable the Virtual Switch function by selecting its mode of operation from the
Mode
pull-down menu.
Select
Done
when the settings have been completely edited.
Figure 4-40. BESTlogic Function Element Screen, 43
Table 4-21 summarizes the BESTlogic settings for Virtual Selector Switches. These settings enable the
x43 element by selecting the mode of operation. There are no logic inputs.
Table 4-21. BESTlogic Settings for Virtual Selector Switches
Function Range/Purpose Default
Mode
0 = Disabled
1 = On/Off/Pulse
2 = On/Off
3 = Off/Momentary On
0
Example 1.
Make the following BESTlogic settings to the Virtual Switch function. See Figure 4-40.
Mode:
On/Off
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......