BE1-CDS220
Testing And Maintenance
13-33
Step 3.
Send to the relay the commands listed in Table 13-18.
Table 13-18. Setup Commands
Command Purpose
A= Gain
access
For 5 A sensing input:
S#-TAP87=MANUAL,2.00,3.80
Set tap 1=2.00 and tap 2=3.80
For 1 A sensing input:
S#-TAP87=MANUAL,0.40,0.76
Set tap 1=0.40 and tap 2=0.76
You can test the relay either by increasing one current from a balanced condition or decreasing it. Refer to
the descriptions of both methods and Sidebar 13-3 to evaluate the differences in the two approaches.
Sidebar 13-3. Maximum Restraint Operating Characteristic
Under maximum restraint, the relay reaches the trip or operate point depending on the level of restraint
as shown in the associated figure. When only one current is changed, the restraint current can vary
depending on the relative changes between currents. When one current is decreased from balance, the
maximum restraint has a vertical characteristic. When increasing one current relative to the other, it will
shift to the right with a sloping characteristic as it continues to increase toward the trip region of the
operate characteristic.
1
2
3
4
5
MAXIMUM RESTRAINT CURRENT (IN MULTIPLES OF TAP)
OPERAT
ING CURRENT
(IN MUL
T
IPL
ES OF
T
AP)
123
Slo
pe
minimum
pickup
increasing current
from balance
decreasing current
from balance
D2857-13.vsd
10-14-99
In order to test the restrained pickup function of the BE1-CDS relay, you may increase one of two
currents initially applied in balance, to create an operate imbalance. In this narrative, the input 1 current
will be the input to be deviated. A similar analysis can be made for deviating input 2 current.
By increasing input current I
1
from balance, I
1trip
is defined as
I
1trip
= I
1balance
/(1-(
100
slope
))in per unit
Sidebar 13-3, Equation 1
with the minimum trip point established as
I
1trip min
= I
1balance
+ minpu in per unit
Sidebar 13-3, Equation 2
where: minpu is the minimum pickup setting
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......