12-24 Installation BE1-CDS220
AØ
BØ
CØ
Circuit
Switcher
P0035-23
01-09-06
With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or delta AC). for more information, refer to Section 3, Input And Output
Functions, Input Current.
Optional independent groupd input (
I
G
) connected to detect low side ground faults.
Phase, Residual, and Negative-Sequence overcurrent elements can be connected to either CT circuit for
backup protectiion. For more information on applying overcurrent backup, refer to Section 8, Application.
(Residual current not available on delta connected CTs.)
Overcurrent neutral ground (
I
N
) operates on internally calculated residual (3I0) current.
For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
Element with the BE1-CDS220 (refer to Figure 12-18 for a connection diagram). To add only metering to
the BE1-CDS220, connect a BE1-MMS100.
1
2
3
1
BE1-CDS220
B2
B1
B3
B4
I
B1
I
A1
1
B10
B14
B12
B9
I
A2
I
B2
I
C2
B13
B11
3
2
X1
X2
X3
3
4
5
Bus or Line
Low Side Breaker
B5
B6
I
C1
B8
B7
I
G
4
H3
H2
H1
A
B
C
C-B
B-A
A-C
C-B
B-A
A-C
DAB
A
B
C
C
A
B
Figure 12-27. Differential Protection of DAC-WYE Grounded Transformer with Y-D CT’s and Optional
Independent Ground Input Connected for Low Side Ground Fault Protection
Summary of Contents for BE1-CDS220
Page 2: ......
Page 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Page 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Page 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Page 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Page 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Page 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Page 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Page 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Page 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Page 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Page 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Page 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Page 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Page 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Page 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Page 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Page 475: ......